Possible measurements
-
Short-circuit loop measurement:
-impedance measurement with 23A current (44A phase-to-phase) - short-circuit resistor R=10Ω,
- measurement range: 95...440V, frequency 45...65Hz,
-
Short-circuit loop measurement with resolution 0,01Ω, in distribution network without tiggering RCD (IΔn≥30mA):
- automatic calculation of short-circuit, detection of phase voltage and phase-to-phase voltage,
- additional UNI-Schuko plug for automatic measurement, AGT adapter for 3 phase network measurement.
-
Testing of general and selective RCD with the rated differential current of 10,30,100,300,500 and 1000mA. (Type AC, A and B).
-
Measurement of insulation resistance:
- with test voltage 250V, 500V, 1000V, 2500V,
- measurement range up to 10GΩ,
- automatic discharging after measurement,
- automatic measurement of all resistences in 3,4,5-wire cables using optional adapter AUTO-ISO,
- acoustic signals in 5sec intervals for insulation resistance characteristic,
- elapsing T1, T2, T3 times (0...600s) form measurement of absorption coefficients (DAR, PI or Ab1, Ab2)
- safety measurement - protection against overvoltage.
-
Measurement of earthing resistance.
-
Bi-directional testing of PE wire continuity using 200mA current.
- Autocalibration of test leads.
-
Phase sequence testing.
-
Memory is divided into 10 memory banks each of them containing 99 memory cells.
-
Battery charge indicator.
-
AUTO-OFF function.
-
USB interface.
Rated operational conditions:
- operation temperature 0...+50°C
Electric security:
- type of insulation: double, according to PN-EN 61010-1and IEC 61557, EMC
- measurement category: IV 300V acc. to PN-EN 61010-1
- protection class acc. to PN-EN 60529: IP54
Short-circuit loop impedance measurement ZL-PE, ZL-N, ZL-L
Measurement using 23/40A current measurement range in accordance with
IEC 61557: 0,13...1999,9Ω
(for 1,2m lead):
Thiết bị phân tích nguồn Sonel MPI-525
Range
|
Resolution
|
Accuracy
|
0,00...19,99Ω
|
0,01Ω
|
±(5% m.v + 3 dgt)
|
20,0...199,9Ω
|
0,1Ω
|
200...1999Ω
|
1Ω
|
rated voltage: 95...270V (forZL-PE i ZL-N) and 95...440V (for ZL-L)
frequency: 45...65Hz
Short-circuit loop impedance measurement ZL-PE RCD
Measurement using 15mA current measurement range in accordance with
IEC 61557: 0,50...1999,9Ω
Range
|
Resolution
|
Accuracy
|
0,00...19,99Ω
|
0,01Ω
|
±(6% m.v. + 10 dgt)
|
20,0...199,9Ω
|
0,1Ω
|
±(6% m.v + 5 dgt)
|
200...1999Ω
|
1Ω
|
rated voltage: 95...270V
frequency: 45...65Hz
Measurement of earthing RE
Rated voltage in accordance with IEC 61557-5: 0,5...1999Ω
Range
|
Resolution
|
Accuracy
|
0,00...9,99Ω
|
0,01Ω
|
±(2% m.v. + 4 dgt)
|
10,0...99,9Ω
|
0,1Ω
|
±(2% m.v. + 3 dgt)
|
100...999Ω
|
1Ω
|
1,00...1,99kΩ
|
0,01kΩ
|
Insulation resistance measurement
Measurement range in accordance with IEC 61557-2:
- for UN = 50V: 50kΩ...250MΩ
- for UN = 100V: 100kΩ...500MΩ
- for UN = 250V: 250kΩ...1GΩ
- for UN = 500V: 500kΩ...2GΩ
- for UN = 1000V: 1MΩ...3GΩ
- for UN = 2500V: 2,5MΩ...9,99GΩ
Range*)
|
Resolution
|
Accuracy
|
0...1999kΩ
|
1kΩ
|
±(3% m.v. + 8 dgt)
|
2,00...19,99MΩ
|
0,01MΩ
|
20,0...199,9MΩ
|
0,1MΩ
|
200...999MΩ
|
1MΩ
|
1,00...3,00GΩ
|
0,01GΩ
|
±(4% m.v. + 6 dgt)
|
1,00...9,99GΩ
|
0,1GΩ
|
*) limited to measurement range.
- with UNI-Schuko additional error ±2%.
Phase sequence
- phase sequence indicator: forward, reverse
- mains voltage range UL-L: 100...440V (45…65Hz) UL-L: 100...440V (45...65Hz)
- display of phase-to-phase voltages
Low voltage test of the circuit and insulation continuity
Test of PE wire continuity using a ±200mA current
Range
|
Resolution
|
Accuracy
|
0,00...19,99Ω
|
0,01Ω
|
±(2% m.v. + 3 dgt)
|
20,0...199,9Ω
|
0,1Ω
|
200...400Ω
|
1
|
- Voltage on open terminals: 4…9V
- Test current at R<2Ω: min. 200mA at rated battery voltage
- Autocalibration of test leads
- Measurements for both polarizations of the current
RCD trigger and response time test tA (for tA mode)
Measurement ranges in accordance with IEC 61557: 0ms ... up to the upper bound of the displayed value
Breaker
Type
|
Test
Current
Multiplier
|
Measurement
Range
|
Resolution
|
Accuracy
|
Standard
|
0,5*IΔn
|
0...300ms
|
1 ms
|
± (2% m.v + 2 dgt)
|
1*IΔn
|
2*IΔn
|
0...150ms
|
5*IΔn
|
0...40ms
|
Selective
|
0,5*IΔn
|
0...500ms
|
1*IΔn
|
2*IΔn
|
0...200ms
|
5*IΔn
|
0...150ms
|
Precision of the differential current: for 0,5*IΔn:-8...0% dla 1*IΔn, 2*IΔn, 5*IΔn: 0...8%
Measurement of the RCD triggering current (IA) for sine waveform testing current
Selected
Current
|
Range
|
Resolution
|
Test
Current
|
Accuracy
|
10mA
|
3,3...10,0mA
|
0,1mA
|
0,3xIΔ..1,0xIΔ
|
± 5% IΔn
|
30mA
|
9,0...30,0mA
|
100mA
|
33...100mA
|
1mA
|
300mA
|
90...300mA
|
500mA
|
150...500mA
|
1000mA
|
330...1000mA
|
1mA
|
It is possible to start the measurement from the positive or negative half of the forced leaking current
Measurement of the RDC triggering current (IA ) for a unidirectional half period sine
waveform test current with a 6mA direct current offset
Selected
Current
|
Range
|
Resolution
|
Test
Current
|
Accuracy
|
10mA
|
4...20,0mA
|
0,1mA
|
0,4xIΔn..2,0xIΔn
|
±10%IΔn
|
30mA
|
12,0...42,0mA
|
0,4xIΔn..1,4xIΔn
|
100mA
|
40,0...140mA
|
1mA
|
300mA
|
120...420mA
|
500mA
|
200...700mA
|
a measurement is possible for a positive or negative forced leakage current
Measurement of the RCD triggering current (IA ) for direct testing current
Selected
Current
|
Range
|
Resolution
|
Test
Current
|
Accuracy
|
10mA
|
4,0...20,0mA
|
0,1mA
|
0,4xIΔn..2,0xIΔn
|
±10%IΔn
|
30mA
|
12,0...60,0mA
|
1mA
|
100mA
|
40...200mA
|
300mA
|
120...600mA
|
500mA
|
200...1000mA
|