Thiết bị phân tích nguồn Sonel MPI-525
	Possible measurements
	- 
		Short-circuit loop measurement:
 -impedance measurement with 23A current (44A phase-to-phase) - short-circuit resistor R=10Ω,
 - measurement range: 95...440V, frequency 45...65Hz,
- 
		Short-circuit loop measurement with resolution 0,01Ω, in distribution network without tiggering RCD (IΔn≥30mA):
 - automatic calculation of short-circuit, detection of phase voltage and phase-to-phase voltage,
 - additional UNI-Schuko plug for automatic measurement, AGT adapter for 3 phase network measurement.
- 
		Testing of general and selective RCD with the rated differential current of 10,30,100,300,500 and 1000mA. (Type AC, A and B).
- 
		Measurement of insulation resistance:
 - with test voltage 250V, 500V, 1000V, 2500V,
 - measurement range up to 10GΩ,
 - automatic discharging after measurement,
 - automatic measurement of all resistences in 3,4,5-wire cables using optional adapter AUTO-ISO,
 - acoustic signals in 5sec intervals for insulation resistance characteristic,
 - elapsing T1, T2, T3 times (0...600s) form measurement of absorption coefficients (DAR, PI or Ab1, Ab2)
 - safety measurement - protection against overvoltage.
- 
		Measurement of earthing resistance.
- 
		Bi-directional testing of PE wire continuity using 200mA current.
 - Autocalibration of test leads.
- 
		Phase sequence testing.
- 
		Memory is divided into 10 memory banks each of them containing 99 memory cells.
- 
		Battery charge indicator.
- 
		AUTO-OFF function.
- 
		USB interface.
	Rated operational conditions:
	- operation temperature 0...+50°C
	Electric security:
	- type of insulation: double, according to PN-EN 61010-1and IEC 61557, EMC
	- measurement category: IV 300V acc. to PN-EN 61010-1
	- protection class acc. to PN-EN 60529: IP54
	Short-circuit loop impedance measurement ZL-PE, ZL-N, ZL-L
	Measurement using 23/40A current measurement range in accordance with
	IEC 61557: 0,13...1999,9Ω
	(for 1,2m lead):
	Thiết bị phân tích nguồn Sonel MPI-525
	
		
			| 
					Range | 
					Resolution | 
					Accuracy | 
		
			| 
					0,00...19,99Ω | 
					0,01Ω | 
					±(5% m.v + 3 dgt) | 
		
			| 
					20,0...199,9Ω | 
					0,1Ω | 
		
			| 
					200...1999Ω | 
					1Ω | 
	
	 
	rated voltage: 95...270V (forZL-PE i ZL-N) and 95...440V (for ZL-L) 
	frequency: 45...65Hz
	Short-circuit loop impedance measurement ZL-PE RCD 
	Measurement using 15mA current measurement range in accordance with 
	IEC 61557: 0,50...1999,9Ω
	
		
			| 
					Range | 
					Resolution | 
					Accuracy | 
		
			| 
					0,00...19,99Ω | 
					0,01Ω | 
					±(6% m.v. + 10 dgt) | 
		
			| 
					20,0...199,9Ω | 
					0,1Ω | 
					±(6% m.v + 5 dgt) | 
		
			| 
					200...1999Ω | 
					1Ω | 
	
	 
	rated voltage: 95...270V
	frequency: 45...65Hz
	Measurement of earthing RE
	Rated voltage in accordance with IEC 61557-5: 0,5...1999Ω
	
		
			| 
					Range | 
					Resolution | 
					Accuracy | 
		
			| 
					0,00...9,99Ω | 
					0,01Ω | 
					±(2% m.v. + 4 dgt) | 
		
			| 
					10,0...99,9Ω | 
					0,1Ω | 
					±(2% m.v. + 3 dgt) | 
		
			| 
					100...999Ω | 
					1Ω | 
		
			| 
					1,00...1,99kΩ | 
					0,01kΩ | 
	
	 
	
	Insulation resistance measurement
	Measurement range in accordance with IEC 61557-2:
	- for UN = 50V: 50kΩ...250MΩ
	- for UN = 100V: 100kΩ...500MΩ
	- for UN = 250V: 250kΩ...1GΩ
	- for UN = 500V: 500kΩ...2GΩ
	- for UN = 1000V: 1MΩ...3GΩ
	- for UN = 2500V: 2,5MΩ...9,99GΩ
	
		
			| 
					Range*) | 
					Resolution | 
					Accuracy | 
		
			| 
					0...1999kΩ | 
					1kΩ | 
					±(3% m.v. + 8 dgt)
 | 
		
			| 
					2,00...19,99MΩ | 
					0,01MΩ | 
		
			| 
					20,0...199,9MΩ | 
					0,1MΩ | 
		
			| 
					200...999MΩ | 
					1MΩ | 
		
			| 
					1,00...3,00GΩ | 
					0,01GΩ | 
					±(4% m.v. + 6 dgt) | 
		
			| 
					1,00...9,99GΩ | 
					0,1GΩ | 
	
	 
	*) limited to measurement range.
	- with UNI-Schuko additional error ±2%.
	Phase sequence
	- phase sequence indicator: forward, reverse
	- mains voltage range UL-L: 100...440V (45…65Hz) UL-L: 100...440V (45...65Hz)
	- display of phase-to-phase voltages
	Low voltage test of the circuit and insulation continuity
	Test of PE wire continuity using a ±200mA current
	
		
			| 
					Range | 
					Resolution | 
					Accuracy | 
		
			| 
					0,00...19,99Ω | 
					0,01Ω | 
					±(2% m.v. + 3 dgt) | 
		
			| 
					20,0...199,9Ω | 
					0,1Ω | 
		
			| 
					200...400Ω | 
					1 | 
	
	 
	- Voltage on open terminals: 4…9V
	- Test current at R<2Ω: min. 200mA at rated battery voltage
	- Autocalibration of test leads
	- Measurements for both polarizations of the current
	RCD trigger and response time test tA (for tA mode)
	Measurement ranges in accordance with IEC 61557: 0ms ... up to the upper bound of the displayed value
	
		
			| 
					Breaker Type
 | 
					Test Current
 Multiplier
 | 
					MeasurementRange
 | 
					Resolution | 
					Accuracy | 
		
			| 
					Standard | 
					0,5*IΔn | 
					0...300ms | 
					
 1 ms
 | 
					
 ± (2% m.v + 2 dgt)
 | 
		
			| 
					1*IΔn | 
		
			| 
					2*IΔn | 
					0...150ms | 
		
			| 
					5*IΔn | 
					0...40ms | 
		
			| 
					Selective | 
					0,5*IΔn | 
					0...500ms | 
		
			| 
					1*IΔn | 
		
			| 
					2*IΔn | 
					0...200ms | 
		
			| 
					5*IΔn | 
					0...150ms | 
	
	 
	Precision of the differential current: for 0,5*IΔn:-8...0% dla 1*IΔn, 2*IΔn, 5*IΔn: 0...8%
	Measurement of the RCD triggering current (IA) for sine waveform testing current
	
		
			| 
					SelectedCurrent
 | 
					Range | 
					Resolution | 
					TestCurrent
 | 
					Accuracy | 
		
			| 
					10mA | 
					3,3...10,0mA | 
					0,1mA | 
					0,3xIΔ..1,0xIΔ | 
					± 5% IΔn | 
		
			| 
					30mA | 
					9,0...30,0mA | 
		
			| 
					100mA | 
					33...100mA | 
					1mA | 
		
			| 
					300mA | 
					90...300mA | 
		
			| 
					500mA | 
					150...500mA | 
		
			| 
					1000mA | 
					330...1000mA | 
					1mA | 
	
	 
	It is possible to start the measurement from the positive or negative half of the forced leaking current
	Measurement of the RDC triggering current (IA ) for a unidirectional half period sine 
	waveform test current with a 6mA direct current offset
	
		
			| 
					SelectedCurrent
 | 
					Range | 
					Resolution | 
					TestCurrent
 | 
					Accuracy | 
		
			| 
					10mA | 
					4...20,0mA | 
					0,1mA | 
					0,4xIΔn..2,0xIΔn | 
					±10%IΔn | 
		
			| 
					30mA | 
					12,0...42,0mA | 
					0,4xIΔn..1,4xIΔn | 
		
			| 
					100mA | 
					40,0...140mA | 
					1mA | 
		
			| 
					300mA | 
					120...420mA | 
		
			| 
					500mA | 
					200...700mA | 
	
	 
	a measurement is possible for a positive or negative forced leakage current
	Measurement of the RCD triggering current (IA ) for direct testing current
	
		
			| 
					SelectedCurrent
 | 
					Range | 
					Resolution  | 
					TestCurrent
 | 
					Accuracy | 
		
			| 
					10mA | 
					4,0...20,0mA | 
					0,1mA | 
					0,4xIΔn..2,0xIΔn | 
					±10%IΔn | 
		
			| 
					30mA | 
					12,0...60,0mA | 
					1mA | 
		
			| 
					100mA | 
					40...200mA | 
		
			| 
					300mA | 
					120...600mA | 
		
			| 
					500mA | 
					200...1000mA |