Thiết bị phân tích nguồn Sonel MPI-502
	The device meets the requirements of EMC standards EN 61326-1:2006 and EN 61326-2-2:2006.
	Electric safety:
	- type of insulation: double, according to EN 61010-1 and IEC 61557
	- measurement category: IV 300V (III 600V) according to EN 61010-1
	- protection class acc. to EN 60529: IP67
	
	Other technical data:
	- dimentions: 220 x 98 x 58mm
	- weight: ~1kg
	- Auto OFF time: 300, 600, 900 second
	- number of measurements Z and RCD (for NiMH batteries): >5000 (2 per minute)
	Short circuit loop impedance measurement ZL-PE, ZL-N, ZL-L
	Measurment using 7,6/13,3A current – Measurement range according to 
	IEC 61557: 0,13...1999Ω
	(for 1,2m lead) and 0,19...1999Ω (for WS-01 and WS-04).
	Thiết bị phân tích nguồn Sonel MPI-502
	
		
			| 
					Display range | 
					Resolution | 
					Accuracy | 
		
			| 
					0,00...19,99Ω | 
					0,01Ω | 
					±(5% m.v. + 3 dgt) | 
		
			| 
					20,0...199,9Ω | 
					0,1Ω | 
		
			| 
					200...1999Ω | 
					1Ω | 
	
	 
	• Nominal work voltage: UnL-N/ UnL-L: 220/380V, 230/400V, 240/415V, 
	• Voltage operating range: 100…264V (for ZL-PE i ZL-N) and 100…440V (for ZL-L), 
	• Nominal network frequency fn: 50Hz, 60Hz, 
	• Max. test current: 23A (230V), 44A (440V), 
	• PE terminal connection corectores check with the help of touch electrode
	Readings of fault loop impedance R and fault loop reactance XL
	
		
			| 
					Display range | 
					Resolution | 
					Accuracy | 
		
			| 
					0,00...19,99Ω | 
					0,01Ω | 
					±(5% m.v. + 5 digits) of ZS value | 
		
			| 
					20,0...199,9Ω | 
					0,1Ω | 
	
	 
	calculated and displayed for ZS<200Ω.
	Short circuit loop impedance ZL-PE in mode RCD – without RCD tripping 
	Measurement using <15mA,current measurement range in accordance with IEC 61557: 0,51...1999,9Ω
	
		
			| 
					Display range | 
					Resolution | 
					Accuracy | 
		
			| 
					0,00...19,99Ω | 
					0,01Ω | 
					±(6% m.v. + 10 dgt) | 
		
			| 
					20,0...199,9Ω | 
					0,1Ω | 
					±(6% m.v. + 5 dgt) | 
		
			| 
					200...1999Ω | 
					1Ω | 
	
	 
	• test without tripping the RCD for IΔn ≥ 30mA,
	• nominal work voltage: Un: 220V, 230V, 240V,
	• voltage operating range:180...270V,
	• frequency operating range fn: 50Hz, 60Hz 
	• PE terminal connection correctness check with the help of touch electrode
	Readings of fault loop impedance R and fault loop reactance XL (without tripping the RCD)
	
		
			| 
					Display range | 
					Resolution | 
					Accuracy | 
		
			| 
					0,00...19,99Ω | 
					0,01Ω | 
					±(6% m.v + 10 dgt) of ZS value  | 
		
			| 
					20,0...199,9Ω | 
					0,1Ω | 
					±(6% m.v + 5 dgt) of ZS value | 
	
	 
	• calculated and displayed for ZS<200Ω.
	RCD parameters test (voltage range 180...270V):
	RCD tripping test and measurment of tripping time tA (for tA function)
	
		
			| 
					Breaker Type | 
					Test CurrentMultiplier
 | 
					Range | 
					Resolution | 
					Accuracy | 
		
			| 
					Standard | 
					0,5*IΔn | 
					0...300ms | 
					
 1 ms
 | 
					
 ± (2% m.v. + 2 dgt)
 | 
		
			| 
					1*IΔn | 
		
			| 
					2*IΔn | 
					0...150ms | 
		
			| 
					5*IΔn | 
					0...40ms | 
		
			| 
					Selective | 
					0,5*IΔn | 
					0...500ms | 
		
			| 
					1*IΔn | 
		
			| 
					2*IΔn | 
					0...200ms | 
		
			| 
					5*IΔn | 
					0...150ms | 
	
	 
	• Precision of the differential current: 0,5*IΔn:-8...0% for 1*IΔn, 2*IΔn, 5*IΔn: 0...8%
	Voltage measurement
	
		
			| 
					Range | 
					Range | 
					Accuracy | 
		
			| 
					0,0V...299,99V | 
					0,1V | 
					±(2% m.v. + 6 dgt) | 
		
			| 
					300V...500V | 
					1V | 
					±(2% m.v + 2 dgt) | 
	
	Frequency measurement
	
		
			| 
					Range | 
					Range | 
					Accuracy | 
		
			| 
					45,0V...65,0Hz | 
					0,1Hz | 
					±(1% m.v. + 1 dgt) | 
	
	 
	Touch voltage measurement referred to the rated residual current (UB)
	
		
			| 
					Range | 
					Resolution | 
					TestCurrent
 | 
					Accuracy | 
		
			| 
					0..9,9V | 
					0,1V | 
					0,4 x IΔn | 
					10% m.v. ± 5 dgt  | 
		
			| 
					10,0..99,9V | 
					0...15% m.v. | 
	
	 
	Measurementof the RCD disconection current IA for sine waveform testing current
	
		
			| 
					SelectedCurrent
 | 
					Range | 
					Resolution | 
					TestCurrent
 | 
					Accuracy | 
		
			| 
					10mA | 
					3,3...10,0mA | 
					0,1mA | 
					0,3 x IΔn...1,0 x IΔn | 
					±5%IΔn | 
		
			| 
					30mA | 
					9,0...30,0mA | 
		
			| 
					100mA | 
					33...100mA | 
					1mA | 
		
			| 
					300mA | 
					90...300mA | 
		
			| 
					500mA | 
					150...500mA | 
	
	 
	• It is posible to start the measurement from the positive or negative half of the forced leaking current
	 
	RCD IA tripping current measurement for unidirectional pulsating residual current
	
		
			| 
					SelectedCurrent
 | 
					Range | 
					Resolution | 
					TestCurrent
 | 
					Accuracy | 
		
			| 
					10mA | 
					4...20,0mA | 
					0,1mA | 
					0,35xIΔn..2,0xIΔn | 
					±10%IΔn | 
		
			| 
					30mA | 
					12,0...42,0mA | 
					0,35xIΔn..1,4xIΔn | 
		
			| 
					100mA | 
					40,0...140mA | 
					1mA | 
		
			| 
					300mA | 
					120...420mA | 
	
	• Measurement is possible for a positive or negative forced leakage current.
	Low voltage test of the circuit and insulation continuity
	Measurement range in accordance with IEC61557:0,12...400Ω
	Test of PE wire continuity using a ±200mA current
	
		
			| 
					Range | 
					Resolution | 
					Accuracy | 
		
			| 
					0,00...19,99Ω | 
					0,01Ω | 
					±(2% m.v + 3 dgt) | 
		
			| 
					20,0...199,9Ω | 
					0,1Ω | 
		
			| 
					200...400Ω | 
					1Ω | 
	
	• Voltage on open terminals: 4…9V,
	• Test current at R<2Ω: min. 200mA,
	• Autocalibration of test leads
	• Measurements for both polarizations of the current
	„m.v.” measured value.