Máy đo điện trở đất và điện trở suất Sonel MRU-21
	It allows to take:
	- earth resistance measurement using auxiliary probes with 3-pole method,
	measurements with max. resistance of auxiliary probes 50kΩ
	- resistance measurement using 2-pole method
	- measurement of continuity of equipotential bondings and protective
	conductors (meeting the requirements of IEC 60364-6-61:2000 section
	6.12.2) with auto-zero function – with current 200mA.
	Additional y:
	- measurement of resistance of auxiliary electrodes R  and R , S H 
	- measurement of interference voltage,
	- high immunity to interference voltage
	-  selection of maximum measuring voltage (25V and 50V),
	- memory of 990 measurement results
	- data transmission to the computer (USB)
	- indication of battery state.
	Electric security:
	- type of insulation double, according to PN-EN 61010-1and IEC 61557
	- measurement category  CAT IV 300V acc. to PN-EN 61010-1
	- protection class acc. to EN 60529  IP54
	Rated operational conditions:
	- operation temperature -10...+55°C
	- storage temperature  -20...+70°C
	- humidity  20...80%
	Other technical data:
	- LCD display  segment, backlit
	- interface  USB
	- number of measurements carried out of set of batteries   > 1000 (5Ω, 2 meas./min.)
	- warranty  3 years
	- dimentions 288x223x75mm
	- weigth 1,4kg
	Measurement of earthing resistance Máy đo điện trở đất và điện trở suất Sonel MRU-21
	measurement range to IEC61557-5: 0,50Ω...1,99kΩ for Un =50V;
	  0,68Ω...1,99kΩ for Un =25V; 
	 
	
		
		
		
	
	
		
			| Range | Resolution | Accuracy | 
		
			| 0,00...9,99Ω | 0,01Ω | ±(2% m.v. + 3 digits) | 
		
			| 10,0...99,9Ω | 0,1Ω | 
		
			| 100...999Ω | 1Ω | 
		
			| 1,00k...1,99kΩ | 0,01kΩ | 
	
	 
	• measurement current: under short circuit >20mA,
	• voltage on open terminals: selectable <25V AC or <50V AC,
	• frequency of measurement current: 125Hz
	 
	Measurement of resistance of auxiliary electrodes R  i R H S
	 
	
		
		
		
		
	
	
		
			| Range | Resolution | Accuracy | 
		
			| 0...999Ω | 1Ω | ±(5% (R +R +R ) + 3 digits) S E H | 
		
			| 1,00k...9,99kΩ | 0,01kΩ | 
		
			| 10,0k...50,0kΩ | 0,1kΩ | 
	
	 
	Measurement of interference voltage U n (RMS)
	 
	
		
		
		
		
	
	
		
			| Range | Resolution | Accuracy | 
		
			| 0...100V | 1V | ±(2% m.v. + 3 digits) |  | 
	
	 
	measurement for DC and AC 45…65 Hz
	 
	Measuremet of continuity of equipotential bondings and protective conductors
	measurement range to IEC61557-4: 0,13Ω...199Ω
	 
	
		
		
		
		
	
	
		
			| Range | Resolution | Accuracy | 
		
			| 0,00...9,99Ω | 0,01Ω | ±(2% m.v. + 3 digits) | 
		
			| 10,0...99,9Ω | 0,1Ω | 
		
			| 100...199Ω | 1Ω | 
	
	 
	- measuring method: technical 2-pole method,
	• max. voltage on open terminals: 13V,
	• measurement current: under short circuit >200mA,
	• auto-zero function for measurement leads